M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)

Product Details
Customization: Available
Phase: Three Phase
Type: Low Frequency

360° Virtual Tour

Diamond Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
3000000 RMB
Plant Area
501~1000 square meters
  • M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)
  • M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)
  • M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)
  • M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)
  • M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)
Find Similar Products

Basic Info.

Model NO.
M33 40-60K
Protection
Overvoltage
Application
Communication
Classification
UPS
Standby Time
Depend on Battery
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Kemapower
Power Source
Electric Power
Transport Package
Safety Packing
Specification
M33-40-60K
Trademark
KEMAPOWER
Origin
China
HS Code
8504402000
Production Capacity
50, 000PCS/Year

Product Description

M33 40K-60K Low Frequency Online UPS

* I/P: 220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY

* O/P:220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY ± 1%

* Capacity:40K/50K/60K

* Output PF: 0.8

* Wave Form:Pure sine wave

* Transfer Time:0 ms

* DC Voltage::384VDC(10K -- 80KVA),396VDC(100K--200KVA)

* Bat.:External Batteries

* Charge Current: 6-30A adjustable



Key features

♦Low frequency three phase on-line double conversion ups 10KVA--400KVA

♦220/380VAC 3P+N+G,110V/208VAC 3P+G optional

♦7 inche touch panel,display detailed running parameter and set the UPS work mode

♦DSP Controlled IGBT inverter

♦Setable UPS/ECO/INVERTER working mode

♦Event log by LCD panel

♦Three-phase separately adjustment to meet 100% unbalance loads

♦Cold start fuction and Auto restarting when mains resume

♦Full protection,overload,over voltage,short circuit,over temperature etc.

♦Static bypass and manual maintenance bypass

♦Advanced Battery Management,temperature compensation charging,setable charge current

♦Automatic charging in UPS off mode

♦RS-232 and Rs485 communication, SNMP or Dry Contact is option

♦Optional input harmonic filter or 12 pulse wave rectifier

♦Optional battery detection modules for per Cell battery

♦Option EPO function

♦Option parallel redundancy



Technical  specifications
Mode  M33-40K M33-50K M33-60K
Nominal capacity KVA  40 50 60
KW  32 40 48
RECTIFIER (INPUT) Phase number Three Phase
Input power factor Standard >= 0.9 ( 6pulse Rectifier+Filter ),  Optional >= 0.96 ( 12pulse Rectifier+Filter)
Input voltage 220/380VAC (230V/400VAC or 240V/415VAC)±25% 3P+N+PE
    110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Input frequency 50Hz±10% or 60Hz±10% (Selectable)
Total Harmonic Distortion (THDi) 6pulse Rectifier<30%, Optional 12pulse Rectifier & Filter<5%
Output ripple wave <2%
Soft start 0-100% 5sec
Charging Charge mode Constant current, then constant voltage, charge with temperature compensation, automatic
switch Between Equalized charging and Float charging,
Folat charging voltage 432VDC
Equalized charging voltage 464VDC
Temeperature compensation voltage -3mV/ºC/cell
Charging current 0.1C(Automatic adjust according to battery capacity)
Charging power 20% of rated capacity
Battery Type  VRLA/AGM/Gel, optional Lithium Battery
Capacity 7~999AH settable (Configurate Battery Capacity according to Back-up Time)
Battery number 32units 12V or 192units 2V batteries (Nominal Voltage 384VDC)
Invertor Phase number Three Phase
Rated power Rated capacity*0.9
Nominal voltage 220/380VAC (230V/400VAC or 240V/415VAC), 3P+N
110V/208VAC( 120V/220VAC or  277V/480VAC )  optional
Output voltage stability ±1%( Stable load), ±3%( fluctuant load)
Frequency stability 50Hz 60Hz<±0.5% ( Asynchronous )
Factor of wave crest >3:1
Output waveform distortion degree Pure Sine Wave, Linear Load< 3%, Non-Linear Load<5%
Dynamic feature Instant voltage<±5% ( from 0 to100% ), Instant recover time<10ms
Unbalance load voltage <±5%
Overload protection At 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S
Invertor efficiency >92%(full load)
Bypass Phase number 3 phase+N
Input nominal voltage 220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC )optional
Output nominal voltage 220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Switching time 0ms(adopted static switch)
Protection Function Input protection Input voltage, frequency over limited protection, Phase fault, Phase lack
Output prorection Over current, short circuit, over voltage, low voltage
Battery protection Over charge, over-discharge protection
Overheat protection Environment over temperature protection, inverter over temperature protection
Hardware fault protection Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc protection
SYSTEM PARAMETERS Work environment Temp: -10~40ºC, relative humidity: 30%~90%, Altitude<2000m ( 1% decrease against 100
meters' rise, max. altitude 4000m )
Cooling method  forced cooling
Communitation interface RS232/ RS485, optional dry contact, SNMP card ( for remote control via Internet)
Parallel operation Tandem hot backup or parallel connection
Anti-surge capacity 10/700μS, 5KV;  8/20μS, 20KA
Protection level lp31
Safety performance Vin-n Vout-n 3000Vac, creepage<3.5mA , insulating resistance>2MΩ(500VDC)
Noise(Db) 48-55
Mechanical dimension(W*D*H)mm 600*720*1500
Weight(Kg) 342 385 402
Remark: all specification subject to change without notice,customer-made specification are acceptable

M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)

Trade Show:

M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)

Certification:
M33-60kVA Triphase Input Double Conversion Online Low Frequency UPS (3: 3)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier