Item |
Model |
RXG1K(T) |
RXG1KS(T) |
RXG2K(T) |
RXG2KS(T) |
RXG3K(T) |
RXG3KS(T) |
Capacity |
VA / Watts (220V) |
1KVA/ 0.9KW |
1KVA / 0.8KW |
2KVA/ 1.8KW |
2KVA / 1.6KW |
3KVA/ 2.7KW |
3KVA / 2.4KW |
VA / Watts (110V) |
1KVA/0.8KW |
1KVA / 0.8KW |
2KVA/1.6KW |
2KVA / 1.6KW |
3KVA/2.4KW |
3KVA / 2.4KW |
Input |
Normal voltage |
220VAC or 110VAC |
Turn on Voltage range |
(90±5~300±5)VAC or ( 60±5-138±5)VAC |
Frequency range |
40~60Hz(adjustable) |
Input power factor |
>0.99(220VAC,full R load) |
Generator |
Support generator input(Generator rating≥2*UPS rating ) |
line low loss/comeback |
220VAC:(110±5)VAC/(125±5)VAC when 30%<load≤60%, 110VAC:(60±3) VAC /(75±3) VAC when load≤60% |
220VAC:(120±5) VAC /(135±5) VAC when 60%<load≤70% 110VAC:(70±3) VAC /(75±3) VAC when 60%<load≤70% |
220VAC:(140±5) VAC /(155±5) VAC when 70%<load≤80%, 110VAC:(70±3) VAC /(85±3) VAC when 70%<load≤80% |
220VAC:(160±5) VAC /(170±5) VAC when load>80%, 110VAC:(80±3 VAC /(85±3) VAC when load>80% |
220VAC:(300±5)VAC/(285±5)VAC when 0%≤load<100%, 110VAC:(138±3)VAC/(133±3)VAC when 0%≤load<100% |
Output |
Voltage range |
200VAC/208VAC/220VAC/230VAC/240VAC/110VAC/120VAC ± 1% , Adjustable by Monitor |
Frequency range |
50Hz/60Hz+-0.2 (Battery mode) |
Wave form |
Pure Sine Wave |
Transfer time |
0 ms (AC mode and battery mode) |
Transfer time: 4ms (typical 2.5ms),AC mode and bypass mode |
Harmonic Distortion |
THD (Linear Load)≤2%,THD (Non-linear Load)≤4% |
Overload capacity |
100%±5%<load warning only, 125%±5%<load≤150%±5% 30s ; 105%±5%<load≤125%±5% 60s,load>150%±5%, 300MS to bypass |
Load peak ratio |
3:1(max) |
Battery |
Installation |
Internal |
External |
Internal |
External |
Internal |
External |
Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery voltage |
36VDC/24VDC |
36VDC |
72VDC/48VDC |
72VDC |
96VDC/72VDC |
96VDC |
Battery number |
3*12V*7AH or 2*12V*7AH |
External |
6*12V*7AH or 4*12V*7AH |
External |
8*12V*7AH 3U or 6*12V*7AH 2U |
External |
Charge Current |
1Amp |
5Amp,Max 7Amp |
1Amp |
5Amp,Max 7Amp |
1Amp |
5Amp,Max 7Amp |
Recharge time |
90%capacity after 5 hrs charging |
depended on battery |
90%capacity after 5 hrs charging |
depended on battery |
90%capacity after 5 hrs charging |
depended on battery |
Bypass |
bypass |
Automatic while overload or ups fail. |
Before ON |
Default ON. Workable set by Winpower |
Voltage Range |
220VAC: 80VAC~286VAC (default: 80VAC~264VAC Could be adjusted by software)/ 110VAC:40VAC~133VAC |
Display |
LED |
Line , Inverter , Bypass, battery |
LCD Option |
input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp.LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. LED for line,bat, Inverter, Bypss |
Audible Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) and every second when battery low |
Overload |
Beeping every 2 min |
Fault |
Beeping Continuously |
Bettery low/charger fault |
Beeping every 1 min |
Bypass mode |
Beeping every 2 min |
L/N inverse |
Beeping every 2 min |
Communications |
RS-232/USB Interface |
RS232 or USB to select , With monitoring software. Default USB |
Working Environment |
Surge protection |
RJ-45 I/O port available for network or Fax/Modem |
Working temperature |
0ºC~40ºC |
Humidity |
0-95% non-condensing |
UPS Product size |
D*W*H(mm) |
450*482.6*88 2U |
450*482.6*88 2U |
665*482.6*88 2U |
450*482.6*88 2U |
665*482.6*132 3U |
450*482.6*88 2U |
UPS CTN size |
D*W*H(mm) |
570*550*225(H) |
570*550*225(H) |
785*560*197(H) |
570*550*225(H) |
785*575*265(H) |
570*550*225(H) |
UPS CTN weight |
Kg/PCS |
15.6 or 18Kg/PCS |
11Kg/PCS |
21.5 or 26Kg |
14Kg/PCS |
26.3 or 36Kg/PCS |
14Kg/1PCS |
Battery pack RBP 607 |
size and weight |
Product size 450*482.6*88 2U, CTN 570*550*225mm(H), CTN G/W: 20Kg |
Battery pack RBP 807 |
size and weight |
Product size 450*482.6*88 2U, CTN 570*550*225mm(H), CTN G/W: 24.5Kg |
OPTION |
Rack Mounting andTower Converter,SNMP, EPO, |
REMARK |
RXG*K (T)--- Standard Type, RXG*KS (T)---- Long Time Type. T: Rack Mounting and Tower Converter |