ITEM |
MODEL |
RXG6K(T) |
RXGC6KS(T) |
RXG10K(T) |
RXG10KS(T) |
Capacity |
VA / Watts |
6KVA/5.4KW |
6KVA/4.8KW |
10KVA/9KW |
10KVA/8KW |
Input |
Normal Voltage |
220VAC, L+N+G |
Input Voltage Range |
100- 280±5V while load≤50% |
150-280±5V, while 50%<load≤80% |
160-280±5V, 80%<load≤90% |
175-280±5V while load>90% |
Frequency Range |
50/60±10% |
Input Power Factor |
>0.99(220VAC,full R load) |
Generator |
Support generator input(Generator rating≥2*UPS rating |
Output |
Voltage Range |
220VAC+-1% |
Frequency Range |
48Hz/54Hz(AC mode), 50HzX(1±0.1%)(Battery mode) |
Waveform |
Pure Sine Wave |
Transfer Time |
0 ms |
Distortion (Full Load) Linear Load |
< 3% |
Distortion (Ful l Load) Nonlinear Load |
< 5% |
Overload Capacity |
105%~125% ,1min then transfer to bypass and alarm. 125%~150% 30s then transfer to bypass and alarm,1min then cut off output. >150% ,0.5s then transfer to bypass and alarm. |
Load Peak Ratio |
3:1(max) |
192VDC Battery PacK |
MODEL |
RBP167 |
N/A |
RBP167 |
N/A |
Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery Voltage |
192VDC |
192VDC |
192VDC |
192VDC |
Battery Capacity |
16*7AH |
External |
16*7AH |
External |
Around backup time (Full load) |
4Mins |
Depended on battery capacity |
3Mins |
Depended on battery capacity |
Around backup time (Half load) |
12Mins |
Depended on battery capacity |
9mMins |
Depended on battery capacity |
Recharge Time |
7 hours to 90%capacity |
Depended on battery capacity |
7 hours to 90%capacity |
Depended on battery capacity |
240VDC Battery Pack |
MODEL |
RBP207 |
N/A |
RBP207 |
N/A |
Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery Voltage |
240VDC |
240VDC |
240VDC |
240VDC |
Battery Capacity |
internal 20*7AH |
External |
internal 20*7AH |
External |
Around Backup Time (Full Load) |
7Mins |
Depended on battery capacity |
5Mins |
Depended on battery capacity |
Around Backup Time (Half Load) |
20Mins |
Depended on battery capacity |
13mMins |
Depended on battery capacity |
Recharge Time |
8 hours to 90%capacity |
5Amp charger |
8 hours to 90%capacity |
5Amp charger |
LED Display |
LED |
Load level / Battery level / Battery mode / Line mode / Inverter /B ypass /Over load / Fault |
LCD Display |
Option |
BAT VDC and % , Input VAC and HZ , Output VAC and HZ, Load W and % ,Temp.Fault Code |
Audible Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) and every second when battery |
Overload |
Beeping twice every second |
UPS Fault |
Beeping Continuously |
Bettery Low/Charger Fault |
Beeping every 1 second |
Bypass Mode |
Beeping every 2 min |
L/N Inverse |
Beeping every 2 min |
Communications |
RS-232 Interface |
With monitoring software. USB Option |
working Environment |
Working Temperature |
,- 20ºC~40ºC |
Humidity |
0-95% non-condensing |
UPS |
Product Size WxDxH (mm) |
483 x 600 x 132(3U) |
483 x 600 x 132(3U) |
483 x 600 x 132(3U) |
483 x 600 x 132(3U) |
Package Size WxDxH (mm) |
795*590*330 |
795*590*330 |
795*590*330 |
795*590*330 |
Gross Weight(Kg) |
27 |
28.5 |
34 |
35 |
RBP167 BAT Pack |
Product Size WxDxH (mm) |
483 x 600 x 132(3U) |
N/A |
483 x 600 x 132(3U) |
N/A |
package Size WxDxH (mm) |
795*590*330 |
N/A |
795*590*330 |
N/A |
Gross Weight(Kg) |
65 |
N/A |
65 |
N/A |
RBP207 BAT Pack |
Product Size WxDxH (mm) |
483 x 600 x 132(3U) |
N/A |
483 x 600 x 132(3U) |
N/A |
package Size WxDxH (mm) |
795*590*330 |
N/A |
795*590*330 |
N/A |
Gross Weight(Kg) |
74 |
N/A |
74 |
N/A |
optional functions |
ECO |
optional |
EPO |
optional |
SNMP |
optional |
REMARK |
RXG*K--- Standard Type, RXG*KS---- Long Time Type |
Option |
Convertor for Option |